![]() Spans for ceiling joists shall be in accordance with Tables R802.4(1) and R802.4(2). Collar ties shall be not less than 1 inch by 4 inches (25 mm by 102 mm) (nominal), spaced not more than 4 feet (1219 mm) on center. Collar ties or ridge straps to resist wind uplift shall be connected in the upper third of the atticspace in accordance with Table R602.3(1). Where ceiling joists or rafter ties are not provided, the ridge formed by these rafters shall be supported by a wall or girder designed in accordance with accepted engineering practice. Rafter ties shall be not less than 2 inches by 4 inches (51 mm by 102 mm) (nominal), installed in accordance with the connection requirements in Table R802.5.1(9), or connections of equivalent capacities shall be provided. Where ceiling joists are not parallel to rafters, rafter ties shall be installed. Where ceiling joists are not connected to the rafters at the top wall plate, joists connected higher in the atticshall be installed as rafter ties, or rafter ties shall be installed to provide a continuous tie. ![]() Ceiling joists shall be continuous or securely joined in accordance with Table R802.5.1(9) where they meet over interior partitions and are nailed to adjacent rafters to provide a continuous tie across the building where such joists are parallel to the rafters. Ceiling joists and rafters shall be nailed to each other in accordance with Table R802.5.1(9), and the rafter shall be nailed to the top wall plate in accordance with Table R602.3(1).